Optidrive Eco

AC Drives for Fan & Pump Control
200 – 600 V Single & 3 phase input
0.75 – 250 kW
1 – 400 HP

ODV-3-240058-3F1E-MN

Optidrive Eco VFD Datasheet

2.2 kW (3 HP), 5.8 A, 380-480 V, 3PH IP66 With Disconnect Outdoor Variable Frequency Drive with EMC Filter and TFT Display

Optidrive Eco

Input Ratings

Supply Voltage 380-480 V
Input Phases 3
Supply Current Continuous 4.7 A
Supply Fuse or MCB (Type B) 6 A

Output Ratings

Motor Output Rating 2.2 kW (3 HP)
Output Voltage 0 – Supply Voltage
Output Current 5.8 A

Cable Information

Max Supply Cable Size 8 mm² (0.01 sq in)
Max Motor Cable Size 8 mm² (0.01 sq in)
Max Motor Cable Length 100 m (328 ft)

Factory Build Options

EMC Filter Internal EMC
Brake Transistor No Brake Transistor
Enclosure IP66 With Disconnect Outdoor
Display TFT Display
PCB Coating Standard

Drive Dimensions
i

Size 2
Height 257 mm (10.12 in)
Width 188 mm (7.4 in)
Depth 182 mm (7.17 in)
Weight 3.5 kg (7.72 lbs)
Fixings 4 x M4

Packaged Dimensions
i

Height 215 mm (8.46 in)
Width 235 mm (9.25 in)
Depth 375 mm (14.76 in)
Weight 4.2 kg (9.26 lbs)